PVE UPS ​

UPS power monitoring via a PVE-UPS appliance — a container that watches your UPS over SNMP and powers off Proxmox VE nodes (and PBS hosts) on a confirmed outage.

Both endpoints this adapter reads (/api/status and /api/health) are public and read-only in PVE-UPS, so there is nothing to authenticate against.

Configuration ​

FieldTypeRequiredDescription
URLURLYesBase URL of the PVE-UPS container (default port 8080)
UPSTextNoPin a single UPS by id or name. Leave blank to roll up every configured device.

The sidebar label is generated from the filename.

Widget Displays ​

  • Power — Mains / On battery / Bypass / No output / Unknown
  • Load percentage
  • Battery charge (tooltip carries the battery status)
  • Estimated runtime
  • Mode — Armed or Dry run
  • Targets — shutdown targets that passed their last self-test
  • Events — warnings and errors from the appliance's 48 hour log

The first four are shown by default; enable the rest in edit mode.

Multiple UPS devices ​

Leave the UPS field blank and the adapter rolls every configured device into one tile, worst-case-wins throughout: load is averaged, charge and runtime take the lowest value, and any unreachable device or active battery takes over the status. The Power tooltip lists each device with its own state.

Pin a device by id or name when you would rather have one tile per UPS.

Status mapping ​

The tile goes amber or red using the same fail-safe rule the appliance itself applies to its shutdown decision — losing contact with a UPS is never treated as a confirmed outage:

Tile stateMeaning
RedAn appliance alarm is active, or a UPS is unreachable
AmberRunning on battery, a low battery, or a target failed its last self-test
GreenOn mains with every shutdown target verified

An unreachable /api/health never reports a failure — the self-test counters are recomputed from /api/status instead, so a dead engine task does not make every target look broken.

Notes ​

  • Runtime shows — while on mains. RFC 1628 leaves the runtime estimate undefined there, and PVE-UPS deliberately refuses to present a stale transfer's counter as a multi-day runtime.
  • Dry run is the safe default: the tile reads Armed only when the appliance reports dry_run: false.
  • pve-ups polls on mains every 30s and on battery every 8s; the adapter matches that with a 15s default polling interval.